The V1000-4X is a version of the standard V1000 in an integral enclosure that meets NEMA type 4X/12 indoor use requirements, UL type 4X/12 standards, and the IP66 rating of IEC 529. This enclosure provides the protection required in tough washdown or dust-tight environments, common in Food and Beverage Processing, Packaging, Metal Machining, Woodworking, Pumping, Refrigeration, and Printing. The enclosure is coated to protect against the harmful effects of sanitizing chemicals commonly used in food industries. Washdown - Dust Tight!

Specifications and Features for V1000-4X Drive


The V1000-4X is a version of the standard V1000 in an integral enclosure that meets NEMA type 4X/12 indoor use requirements, UL type 4X/12 standards, and the IP66 rating of IEC 529. This enclosure provides the protection required in tough washdown or dust-tight environments, common in Food and Beverage Processing, Packaging, Metal Machining, Woodworking, Pumping, Refrigeration, and Printing. The enclosure is coated to protect against the harmful effects of sanitizing chemicals commonly used in food industries.

Performance Features
  • Ratings: 1/8 to 5 HP at 240 VAC 1-ph,
    1/8 to 25 HP (ND) at 240 VAC 3-ph, 
    1/2 to 25 HP (ND) at 380-480 VAC 3-ph
  • Overload Capacity:
    150% for 60 sec. (Heavy Duty)
    120% for 60 sec. (Normal Duty)
  • Control Methods: V/f Control,
    Open Loop Current Vector Control,
    PM Open Loop Current Vector Control
    Simple closed loop speed control
  • DC injection braking, ramp to stop
  • Electronic reversing
  • Adjustable accel/decel:0.01 to 6000 seconds
  • Controlled speed range:
    40:1(1) 100:1(2)
  • Speed Regulation:
    ± 0.5 to 1% with slip compensation(1)
    ± 0.2%(2)
  • Displacement power factor: 0.98
  • Output frequency: 0 to 400 Hz
  • Frequency resolution:
    0.01 Hz with digital reference
    0.06 / 60 Hz with analog reference
  • Frequency accuracy:
    0.01% with digital command
    0.5% with analog command
  • Volts / hertz ratio: infinitely adjustable pattern
  • DC Injection braking: adjustable amplitude, duration, current limited
  • Torque boost: full range, auto
  • Power loss ride-thru: 0.5 sec.
  • Speed search
  • Auto restart
  • 3 Critical frequency rejection settings
  • Slip Compensation
  • Energy $avings Function
  • Enhanced PID with loss of feedback function
Protective Features
  • Current limit, stall prevention during accel, decel, and run
  • Motor and drive overload
  • Over voltage prevention function
  • Instantaneous over current
  • Short circuit
  • Under voltage
  • Heatsink overheat
  • Ground fault protection
  • Over/under torque
  • Short circuit current rating: 30KA RMS
Options
  • 120VAC Interface
  • Profibus-DP, DeviceNet Communications
  • Modbus TCP/IP, EtherNet/IP Communications
  • DriveWizard Plus
  • Y-Stick Copy Unit
Design Features
  • Dual microprocessor logic
  • Digital keypad operator, 5 digits
  • LED status display
  • Remote Mount Keypad Capability
  • RJ-45 Style Digital Operator Connector
  • 7 multifunction digital inputs
  • 3 multifunction digital outputs
  • Hardwire baseblock (EN954-1 Cat. 3)
  • Programmable form C output contact for customer use: 1A at 250 VAC or 30 VDC
  • 24 VDC control logic compatible with sourcing or sinking outputs (PNP or NPN)
  • Carrier frequency: 15 kHz max; swing PWM
  • 16 multi-speed settings plus jog speed
  • 2 Remote speed references
    0-10 VDC (20 kohms) or isolated 4-20 mA (250 ohms)
  • Signal follower: bias and gain
  • 2 programmable open collector outputs
  • Analog monitor output:
    0-10 VDC proportional to output frequency or output current
  • Approx. 400 parameters & monitors
  • Digital pulse train input (33 kHz max.)
  • Cooling fan controlled by drive run/stop
  • RS-422/485 MODBUS 115 kbps
  • UL recognized electronic overload
  • MTBF 28 years
  • Built-in Dynamic Braking Transistor
  • NEMA 4X/IP66 enclosure
  • Application Presets
  • Maintenance monitors
Service Conditions
  • Ambient service temperature:
    -10° to 40°C (+14° to 104°F) NEMA 1
    -10° to 50°C (+14° to 122°F) Open Chassis
  • Ambient storage temperature:
    -20° to 60°C (-4° to 140°F)
  • Humidity: to 95% non-condensing
  • Altitude: to 3300 ft; higher by derating
  • Service factor: 1.0
  • Input voltage: -15% to +10%
    200 to 240 VAC, 380 to 480 VAC
  • Input frequency: +/-5%; 50/60 Hz
  • Input Phase sequence insensitive
Standards
  • UL 508C (Power Conversion)
  • CSA 22.2 No. 14-95 (Industrial Control Equipment)
  • UL, cUL listed; CE marked
  • RoHS compliant
  • EN 50178 (LVD)
  • EN 50081-2, EN 50082-2 (EMC)
  • EN 954-1, Category 3 Safety Standard
  • EN 61800-3
  • IEC 529, 146
  • FCC CFR 47 Part 15 Subpart B (w/ External Filter)
  • TUV
  • NEMA type 4X/12

Control Methods:(1) V/f Mode, (2) Open Loop Vector Mode

Models & Ratings for V1000-4X Drive


V1000-4X Drives - 1/8-25HP, NEMA Type 4X/12 enclosure

200-240V 1-Phase200-240V 3-Phase380-480V 3-Phase

Rated Input Voltage
Drive Model Number
Normal Duty1
Heavy Duty1
Standard Enclosure
Rated Output
Current (Amps)
Nominal HP2
Rated Output
Current (Amps)
Nominal HP2
200-240V, 1-Phase
CIMR-VUBA0001GAA
1.2
1/8 & 1/4
0.8
1/8
NEMA Type 4X/12
CIMR-VUBA0002GAA
1.9
1/4
1.6
1/4
200-240V, 1-Phase
CIMR-VUBA0003GAA
3.3
1/2 & 3/4
3
1/2
NEMA Type 4X/12
CIMR-VUBA0006GAA
6
1
5
3/4 & 1
200-240V, 1-Phase
CIMR-VUBA0010GAA
9.6
2 & 3
8
2
NEMA Type 4X/12
CIMR-VUBA0012GAA
12
3
11
3

 

Rated Input Voltage
Drive Model Number
Normal Duty1
Heavy Duty1
Standard Enclosure
Rated Output
Current (Amps)
Nominal HP2
Rated Output
Current (Amps)
Nominal HP2
200-240V, 3-Phase
CIMR-VU2A0001GAA
1.2
1/8 & 1/4
0.8
1/8
NEMA Type 4X/12
CIMR-VU2A0002GAA
1.9
1/4
1.6
1/4
CIMR-VU2A0004GAA
3.5
1/2 & 3/4
3
1/2
200-240V, 3-Phase
CIMR-VU2A0006GAA
6
1
5
3/4 & 1
NEMA Type 4X/12
CIMR-VU2A0010GAA
9.6
2 & 3
8
2
CIMR-VU2A0012GAA
12
3
11
3
200-240V, 3-Phase
CIMR-VU2A0020GAA
19.6
5
17.5
5
NEMA Type 4X/12
CIMR-VU2A0030GAA
30
7.5 & 10
25
7.5
CIMR-VU2A0040GAA
40
10
33
10
200-240V, 3-Phase
CIMR-VU2A0056GAA
56
15 & 20
47
15
NEMA Type 4X/12
CIMR-VU2A0069GAA
69
20 & 25
60
20

 

Rated Input Voltage
Drive Model Number
Normal Duty1
Heavy Duty1
Standard Enclosure
Rated Output
Current (Amps)
Nominal HP2
Rated Output
Current (Amps)
Nominal HP2
380-480V, 3-Phase
CIMR-VU4A0001GAA
1.2
1/2
1.2
1/2
NEMA Type 4X/12
CIMR-VU4A0002GAA
2.1
3/4 & 1
1.8
3/4
380-480V, 3-Phase
CIMR-VU4A0004GAA
4.1
2
3.4
1 & 2
NEMA Type 4X/12
CIMR-VU4A0005GAA
5.4
3
4.8
3
380-480V, 3-Phase
CIMR-VU4A0007GAA
6.9
4
5.5
3
NEMA Type 4X/12
CIMR-VU4A0009GAA
8.8
5
7.2
4
380-480V, 3-Phase
CIMR-VU4A0011GAA
11.1
7.5
9.2
5
NEMA Type 4X/12
CIMR-VU4A0018GAA
17.5
10
14.8
7.5 & 10
380-480V, 3-Phase
CIMR-VU4A0023GAA
23
15
18
10
NEMA Type 4X/12
CIMR-VU4A0031GAA
31
20
24
15
CIMR-VU4A0038GAA
38
25
31
20

 

  1. Normal Duty overload current rating is 120% of rated output current for 60 seconds; Heavy Duty overload current rating is 150% of rated output current for 60 seconds
  2. Horsepower rating is based on 230 Volt and 460 Volt Induction-Type Squirrel Cage NEMA B 4-Pole Motors as represented in NEC Table 430.250 Full-Load Current, Three-Phase Alternating-Current Motors.
 