You are here :: Adroit >> Associates >> L & T- Yaskawa >> Drives & Motors >> AC Drives
F7 Drive E-mail
F7 Drive
1/2 - 500 Horsepower Industrial Workhorse

The F7 drive is the Industrial Workhorse of adjustable frequency drives. It is intended to handle every conventional drive application found in the typical industrial manufacturing plant from simple variable torque pumping to sophisticated networked material handling. With excellent performance and a wide array of configurations and options, the F7 can be the single drive platform for an entire facility. Network communications, plug-in I/O cards, custom software, and power/packaging options are among the many choices.

For new installations or retrofits, the F7 is truly the Industrial Workhorse, perfect for every conventional application…and even some unconventional ones.

The F7 / Configured package provides an F7 drive in a NEMA Type 12 or NEMA 12 FVFF enclosure, with space for factory-mounted and wired options, such as reactors, filters, circuit breakers, fuses, network communications and I/O cards, etc.

Specifications and Features for F7 Drive


The F7 Drive: This AC drive is the Industrial Workhorse that can handle every conventional application found within the typical industrial plant, from simple variable torque pumping to sophisticated networked material handling. All of this is possible with the smart and flexible design platform of the F7, providing both Normal and Heavy Duty ratings, four modes of control, network communication options, application-specific drive software, and an array of standard and optional input/output choices.

The F7 is factory-programmed and ready to run. For operational simplicity and clarity, the LCD operator display has 5 lines x 16 characters. It can be set to any of 7 languages. The keypad is intuitive and includes parameter copying to move a chosen set of parameters from one drive to another. If the application requires programming, the F7 makes it easy. Parameters are grouped in easy to use sets; quick start and advanced. To enhance parameter and data management, DriveWizard software for the PC is available at no charge, for upload/download, trending, and graphing.

This drive is designed for tough industrial environments. It is rugged and reliable, with an MTBF of 28 years. A variety of enclosure options provide the right environmental protection. The dual ratings, Normal and Heavy duty, enable the most economical match of overload capacity and starting torque for the application. Providing the right fit to power requirements is also easy with 208/240 and 480 volt ratings, built-in bus choke above 30 HP, 12-pulse capability above 30 HP, common bus capability, and regeneration options. Patented high slip braking can eliminate the need for dynamic braking resistors for high inertia loads. Other features include motor auto-tuning and a wide range of configurable options, such as breakers and fuses.

To provide the optimum control method, the F7 can operate in conventional V/f, V/f with encoder feedback, open loop vector, or closed loop vector mode. Drive performance can be further enhanced for a specific application with optional software.

The F7 supports the industry’s open architecture, open connectivity demands with network communications choices such as DeviceNet, Profibus-DP, and others. Drive coordination with other equipment is simplified with inputs and outputs for digital pulse train, 4 to 20 mA, -10 to +10 V, and an assortment of programmable contacts.

For new installations or retrofits, the F7 is truly the Industrial Workhorse, perfect for every conventional application…and even some unconventional ones

Performance Features
  • Ratings:
    0.5 to 150 HP, 208 to 240 VAC
    0.75 to 500 HP, 480 VAC
  • Overload capacity:
    150% for 1 min heavy duty, nominal 110% for 1 min normal duty
  • Starting torque:
    150%, at 1Hz (V/f), at 0.5 Hz (open loop), at 0.3 Hz (closed loop)
  • Output frequency: 
    0.01 to 300 Hz for heavy duty, 400 Hz for normal duty
  • Controlled speed range:
    40:1 (V/f), 50:1 (V/f with PG), 200:1 (open loop), 1000:1 (closed loop)
  • Speed regulation:
    2-3% (V/f), 0.02% (V/f with PG), 0.2% (open loop), 0.01% (closed loop)
  • Speed/frequency resolution:
    0.01% with digital reference, 0.1% with analog reference, 0.1 Hz with Modbus
  • Electronic reversing
  • Adjustable accel/decel: 0.1 to 6000 sec
  • Stall prevention
  • Drive efficiency: 96 to 98%
  • Displacement power factor: 0.98
  • Power loss ride-thru: 2 sec
  • Inertial ride-thru
  • Selectable auto restart after momentary power loss
  • Programmable auto restart
    (0 to 10 attempts) on re-settable fault
  • Critical frequency rejection: 3 selectable, adjustable bands
Protective Features
  • DC bus CHARGE indicator
  • Optically-Isolated controls
  • Phase-to-phase / phase-to-neutral short circuit protection
  • Ground fault protection
  • Electronic motor overload (UL)
  • Current and torque limit
  • Over-torque / under-torque detection
  • Fault circuit: over-current, over-voltage, and over-temperature
  • Input/output phase loss
Inputs and Outputs
  • Analog inputs:
    -10 to +10 VDC (20K ohms) or 4 to 20 mA (250 ohm)
  • Analog outputs:
    -10 to +10 VDC or 4-20 mA proportional to output parameters
  • Digital pulse train input/output (32 KHz max)
  • Digital Inputs: 8 multi-function
  • Programmable outputs: Three form A
  • Fault contacts: form C
  • RS-485/422 communication terminals
Additional Features for V/f
  • Torque boost: full range, auto
  • V/f ratio: 15 preset, one adjustable
  • Slip compensation
Design Features
  • LCD keypad display, 5 lines x 16 characters, backlit, 7 languages, copy function
  • Multi-speed settings: 17 available
  • Setpoint (PID) trim control
  • Signal follower: bias and gain
  • Up / down / hold reference (digital M.O.P.)
  • Timer function; on/off delay
  • 32-bit microprocessor logic
  • Easy access, quick start parameter groups
  • Nonvolatile memory/program retention
  • Flash memory for update and custom applications
  • 24 VDC control logic
  • DC injection braking, adjustable level
  • Dynamic braking
  • High-slip braking
  • Ramp to stop or coast to stop
  • Dual motor parameter sets
  • Synchronized start into rotating motor
  • Motor auto-tuning, static and dynamic
  • Common bus capability
  • DC link choke: 30 to 150 HP at 240 VAC, 30 to 500 HP at 480 VAC
  • Twelve-pulse capability: 30 to 150 HP at 240 VAC, 30 to 500 HP at 480 VAC
  • Terminal strip, quick disconnect
  • Split cover for easy wiring
  • Plug-in heat sink fan
Service Conditions
  • Ambient service temperatures:
    -10 to 40°C (104°F) NEMA 1, to 45°C (113°F) protected chassis
  • Humidity: non-condensing 95%
  • Altitude: to 3300 feet (1000 meter)
  • Input voltage: +10% / -15%, 3 phase
    200 to 240 VAC, 380 to 480 VAC
  • Enclosure: NEMA 1 or protected chassis (other options)
  • Input frequency: 50/60 Hz ± 5%
  • 3-phase, 3-wire phase insensitive
  • Vibration: 1G, (10 to 20Hz), 0.2G (20 to 50Hz)
Standards & Reliability
  • UL, cUL & CE listed
  • IEC: 146A
  • MBTF: Exceeds 28 years
  • Tested on fully-loaded motors
  • Surface mount technology

Models & Ratings for F7 Drive


F7 Standard Drives
- 1/2-500HP, 3-phase1 input, NEMA 1 or protected chassis enclosure

208V240V230V480V

Rated Input Voltage
Drive Model Number
CIMR-F7
Normal Duty2
Heavy Duty2
Standard Enclosure
Rated Output Current (Amps)
Nominal HP3
Rated Output Current (Amps)
Nominal HP3
208V
CIMR-F7U20P41
3.6
1/2
3.2
1/2
NEMA 1
3/4
208V
CIMR-F7U20P71
4.6
1
4.2
3/4
NEMA 1
CIMR-F7U21P51
7.8
2
7.0
1
208V
CIMR-F7U22P21
10.8
3
9.6
2
NEMA 1
CIMR-F7U23P71
16.8
5
15.2
3
208V
CIMR-F7U25P51
23
N/A
23
5
NEMA 1
208V
CIMR-F7U27P51
31
7.5
31
7.5
NEMA 1
10
10
208V
CIMR-F7U20111
46.2
15
45
N/A
NEMA 1
CIMR-F7U20151
59.4
20
58
15
208V
CIMR-F7U20181
74.8
25
71.4
20
NEMA 1
CIMR-F7U20221
88
30
85
25
208V
CIMR-F7U20301
115
40
115
30
NEMA 1
40
208V
CIMR-F7U20370
162
50
145
50
Protected Chassis
CIMR-F7U20450
192
60
180
60
208V
CIMR-F7U20550
215
75
215
75
Protected Chassis
CIMR-F7U20750
312
100
283
100
208V
CIMR-F7U20900
360
125
346
125
Protected Chassis
CIMR-F7U21100
415
150
3604
150

 

Rated Input Voltage
Drive Model Number
CIMR-F7
Normal Duty2
Heavy Duty2
Standard Enclosure
Rated Output Current (Amps)
Nominal HP3
Rated Output Current (Amps)
Nominal HP3
240V
CIMR-F7U20P41
3.6
1/2
3.2
1/2
NEMA 1
3/4
3/4
240V
CIMR-F7U20P71
4.6
1
4.2
1
NEMA 1
CIMR-F7U21P51
7.8
2
7
2
240V
CIMR-F7U22P21
10.8
3
9.6
3
NEMA 1
CIMR-F7U23P71
16.8
5
15.2
5
240V
CIMR-F7U25P51
23
7.5
23
7.5
NEMA 1
CIMR-F7U27P51
31
10
31
10
240V
CIMR-F7U20111
46.2
15
45
15
NEMA 1
CIMR-F7U20151
59.4
20
58
20
240V
CIMR-F7U20181
74.8
25
71.4
25
NEMA 1
CIMR-F7U20221
88
30
85
30
CIMR-F7U20301
115
40
115
40

 

Rated Input Voltage
Drive Model Number
CIMR-F7
Normal Duty2
Heavy Duty2
Standard Enclosure
Rated Output Current (Amps)
Nominal HP3
Rated Output Current (Amps)
Nominal HP3
230V
CIMR-F7U20370
162
50
60
145
50
Protected Chassis
CIMR-F7U20450
192
75
180
60
230V
CIMR-F7U20550
215
N/A
215
75
Protected Chassis
CIMR-F7U20750
312
100
125
283
100
230V
CIMR-F7U20900
360
150
346
125
Protected Chassis
CIMR-F7U21100
415
N/A
3604
150

 

Rated Input Voltage
Drive Model Number
CIMR-F7
Normal Duty2
Heavy Duty2
Standard Enclosure
Rated Output
Current (Amps)
Nominal HP3
Rated Output Current (Amps)
Nominal HP3
480V
CIMR-F7U40P41
1.8
1/2
1.8
1/2
NEMA 1
3/4
3/4
480V
CIMR-F7U40P71
2.1
1
2.1
1
NEMA 1
CIMR-F7U41P51
3.7
2
3.7
2
480V
CIMR-F7U42P21
5.3
3
5.3
3
NEMA 1
CIMR-F7U43P71
7.6
5
7.6
5
480V
CIMR-F7U45P51
12.5
7.5
12.5
7.5
NEMA 1
CIMR-F7U47P51
17
10
17
10
480V
CIMR-F7U40111
27
15
24
15
NEMA 1
20
480V
CIMR-F7U40151
34
25
31
20
NEMA 1
CIMR-F7U40181
40
30
39
25
480V
CIMR-F7U40221
50.4
N/A
45
30
NEMA 1
480V
CIMR-F7U40301
67.2
40
60
40
NEMA 1
50
480V
CIMR-F7U40371
77
60
75
50
NEMA 1
CIMR-F7U40451
96
75
91
60
CIMR-F7U40551
125
100
112
75
480V
CIMR-F7U40750
156
125
150
100
Protected Chassis
480V
CIMR-F7U40900
180
150
180
125
Protected Chassis
150
480V
CIMR-F7U41100
240
200
216
N/A
Protected Chassis
CIMR-F7U41320
260
N/A
260
200
480V
CIMR-F7U41600
304
250
304
250
Protected Chassis
480V
CIMR-F7U41850
414
300
370
300
Protected Chassis
350
480V
CIMR-F7U42200
515
400
4145
350
Protected Chassis
450
480V
CIMR-F7U43000
675
5905
450
Protected Chassis
500
500

 

  1. Contact us at 800-YASKAWA (927-5292) for single phase applications and sizing.
  2. Normal Duty overload current rating is 110% of rated output current for 60 seconds; Heavy Duty overload current rating is 150% of rated output current for 60 seconds
  3. Horsepower rating is based on standard NEMA B 4-pole motor design as represented in NEC table 430. 150 Full-Load Current, Three-Phase Alternating Current Motors
  4. 138% OL for 60secs
  5. 150% OL for 45secs
 
© 2010 Adroit Control Systems Pvt. Ltd. All Rights Reserved.