You are here :: Adroit >> Associates >> Rishabh >> Elect. Transducer
RISH Ducer M20 E-mail

RISH Ducer M20

Features :

  • Programmable for specific systems (1/3 phase, 2/3/4 wire)
  • Nominal current programmable from 1 to 6 A
  • Nominal voltage programmable from 57V to 400 V (Phase-to-neutral), or 100V to 693 V (phase-to-phase)
  • Programmable analog outputs (Current or Voltage)
  • Digital outputs can be used for limit value monitoring or energy metering
  • Programmable Bend Characteristics
  • Programmable Response time
  • Universal (AC,DC) power pack with very wide tolerance range or AC auxiliary supply.
  • Configurable from a PC or RS 232 interface

General- The following ancillary functions are available :

  • Power system check
  • Display of measurement values at a PC monitor
  • Simulation of outputs
  • Recording of data in excel file & more


Analog Output

2

Digital Output

0

Interface

RS 232

Measured Variables

Current & Voltage, Active/Reactive & Apparent Power,Cosφ,Sinφ & Power Factor, Ampere Demand,Frequency, Energy

Systems

Single Phase AC,3Phase 3 wire Balanced/Unbalanced load, 3 Phase 4 wire Balanced/Unbalanced load

INPUTS

Frequency

Nominal Voltage

Nominal Current

50 to 60 Hz, 16 ⅔ Hz

57V to 400V

1A to 6A

Continuous
Overload
Capacity

Current

Voltage

10A

480V single phase sys 813 V Three phase sys

OUTPUTS

Load Independent
DC Current

Load Independent
DC Voltage

1mA to 20 mA

1V to 10V

Accuracy:
DIN IEC 688

Frequency

Current/Voltage

Power&Power Factor

0.15%

0.2%

0.25%

Power
Supply

AC Voltage

DC/AC Voltage

100V,110V,230V,400V,500V or 693 V

24V to 60V or 85V to 230V

Response Time

1…2 times the measurement cycle

Measurement Cycle

Approx. 0.25 sec to 0.5 sec for 50Hz












 
© 2010 Adroit Control Systems Pvt. Ltd. All Rights Reserved.