Programmable universal transmitter RISHDucer V604, converts the input variable- a DC current or voltage, or a signal from a thermocouple, resistance thermometer, remote sensor or potentiometer - to a proportional analog output signal.
Features :
|
Input variable (Resistance, DC current, DC voltage, Potentiometer) and all measuring ranges programmed using PC.
|
|
Output signal range and characteristics(linear/bent/live zero) are programmed using PC and the type of output signal (current or voltage) on a DIP switch.
|
|
Electrical isolation between measured variable, analog output signal and power supply as per EN 6 1010
|
|
Measured variable data available at the programming interface.
|
|
Measured variable and signals can be viewed on site using a PC.
|
Measuring Input :
|
B, E, J, K, L, N, R, S, T, U W5 - W26 Re
|
|
Pt 100, Ni 100, Pt 20/20 °C , Cu 10/25 °C, Cu 20 / 25 °C, 2,3 or 4wire connection
|
|
0...8Ω to 0....5kΩ
|
|
0...80m A to 0...100 mA
|
|
0...2 mV to 0...40 V
|
Cold Junction compensation Internal : Incorporated resistor Ni 100
DC current :
|
Ranges
|
0 ... 20 or 4 ... 20 mA limit ± 22mA
|
|
Burden Voltage
|
+15 V, resp - 12v
|
DC voltage :
|
Ranges
|
0... 5, 1 ...5, 0...10 or 2... 10V
|
|
limit
|
12V to + 15V
|
|
Load capacity
|
20mA
|
|
Power Supply
|
24 V . . . 60 V DC/AC and 85 V . . . 230 V DC/AC
|
|
Accuracy
|
± 0.5%
|
Inputs & Outputs available
1 input - 2 outputs
LED Display :
|
Green LED
|
For indicating device in operating condition
|
|
Red LED
|
For indicating operation of open-circuit or trip point
|
|
Optional
|
Connector RS 232 Programming Kit with software
|
|